Methodology
Every figure below was transcribed at build time from a published document, never from recollection. The extracted source text is committed in the repository, and each figure carries the verbatim sentence it came from so you can check it without taking our word for anything.
What this does not cover
- Only 4 jurisdictions. Zoning setbacks, noise limits and screening rules are entirely local, and they routinely govern over both the manufacturer and the model code. For anywhere not listed below, the tool gives you the other two layers and says plainly that the local one is missing. It will not guess.
- Only 3 manufacturer families.Named models only — we do not extrapolate one family’s figures onto another, because they genuinely differ.
- No HOA or deed data. HOA and deed restrictions (CC&Rs) are not checked. There is no public per-address source for them, so we do not pretend to have one. CC&Rs routinely impose screening, placement and noise terms stricter than anything above, and they are enforceable against you independently of the building permit. Read your CC&Rs, and get any HOA architectural-review approval in writing before the pad is poured.
- Anchoring is surfaced, not calculated. Where a jurisdiction imposes a wind-resistance requirement we state it and the certification it triggers. We do not perform a structural calculation.
- This is a design aid. A competent person must check the schedule, and the authority having jurisdiction has the final say.
Findings worth knowing
The fire-test reduction applies to the wall, not to openings. NFPA 37 §4.1.4 requires 5 ft both from combustible walls and from openings in walls. Generac’s Southwest Research Institute listing reduces the wall figure to 18 in. It does not reduce the 5 ft to openings. Conflating the two is the most common way a placement fails inspection.
Manufacturer geometries are not interchangeable. Generac states one rear figure around a broadly symmetric envelope. Cummins states four different per-face figures. A Cummins unit positioned to a Generac diagram can be non-compliant on three sides at once.
Clearances do not vary by kW. Every source document we read publishes one clearance set for a whole product family. Sizing the generator changes the load calculation, the gas supply and the pad — not these distances.
Florida is materially stricter than NFPA 37. FBC Residential §M1905.2.5 requires 10 ft to openings, double the model-code figure, reducible to 5 ft only where the carbon monoxide alarm conditions are met.
Kohler publishes no numeric structure clearance in TP-6803’s body text. It defers to state and local codes and to a dimension drawing that is vector art rather than text. We report that gap as unresolved rather than filling it with another manufacturer’s number.
Manufacturer listings
Generac Air-cooled home standby
Guardian and PowerPact air-cooled home standby, 9 kW–22 kW (60 Hz) · 9–22 kW (the companion owner's manual covers 10–24 kW with the same placement guidance)
Source: Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)
- 18 in (457 mm)structure · rear
18 in from an existing wall at the rear, where the fuel and electrical connections are made.
“Fuel and electrical connections are made here. 18 in (457 mm) minimum clearance per NFPA testing, labeling, and listing, unless state or local codes dictate otherwise. … The generator should not be placed closer than 18 in (457 mm) from existing walls.”
Generac Install. Guidelines, Figure 3-2, items B and D Exception → 5 ft (1524 mm)
The 18 in figure is a listing-based reduction from NFPA 37's 5 ft. Where state or local codes do not accept the SwRI listing, the unreduced NFPA 37 §4.1.4 figure of 5 ft applies.
- State or local code declines the SwRI listing, which the manual expressly allows for ("unless state or local codes dictate otherwise").
- 3 ft (914 mm)serviceAccess · front
3 ft clear in front, including shrubs, bushes and trees.
“Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.”
Generac Install. Guidelines, Figure 3-2, item A - 3 ft (914 mm)serviceAccess · endA
3 ft clear at the ends, including shrubs, bushes and trees.
“Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.”
Generac Install. Guidelines, Figure 3-2, item A - 3 ft (914 mm)serviceAccess · endB
3 ft clear at the ends, including shrubs, bushes and trees.
“Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.”
Generac Install. Guidelines, Figure 3-2, item A - 5 ft (1524 mm)structure · top
5 ft from any structure, overhang or projection above the unit. Never under a wooden deck or structure.
“5 ft (1.52 m) minimum distance from any structure, overhang, or projections from wall. DO NOT install under wooden decks or structures.”
Generac Install. Guidelines, Figure 3-2, item F - 5 ft (1524 mm)opening · all
5 ft from any opening in a wall, measured from any point of the generator. The SwRI listing reduces the distance to the WALL, not the distance to OPENINGS.
“No operable windows, doors, vents, window wells, or openings in the wall are permitted near any point of the generator. … Engines … installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls …”
Generac Install. Guidelines, Figure 3-2 item C, with NFPA 37 §4.1.4 at p. 16 - 10 ft (3048 mm)airIntake · all
10 ft horizontally from an HVAC supply-air outdoor intake opening.
“IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for HVAC supply air systems shall be located not less than 10 feet (3048mm) horizontally from the generator enclosure. See Section 401 in the ICC Mechanical Code for any additional requirements.”
Generac Install. Guidelines, p. 14, item J (Make up air system) - 3 ft (914 mm)serviceAccess · front
A removable fence panel may not sit closer than 3 ft in front of the unit.
“A removable barrier (non-permanent; without footings) installed as a visual surround. Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the generator.”
Generac Install. Guidelines, Figure 3-2, item E
Cummins RS home standby
RS13A; RS17A; RS20A; RS20AC · 13–20 kW
Source: Cummins, Installation Manual A053X172 (Issue 16), 5-2019
- 5 ft (1524 mm)opening · all
60 in from any opening in a wall of a structure that may be occupied, measured from ALL parts of the enclosure.
“All parts of the generator set enclosure must be at least 60 inches (1524 mm) from any openings in walls of structures that may be occupied. Examples of wall openings include but are not limited to: operable windows, doors, dryer vents, fresh air intake for heaters, etc.”
Cummins A053X172, §4 Installation, Picking a Location - 18 in (457 mm)structure · serviceSide
One of the engine/alternator sides at not less than 18 in from a combustible wall, kept free of obstruction for service access.
“One side (either engine or alternator) must be located not less than 18 inches (458 mm) from any structures having combustible walls. This space must be free of any obstructions for service access.”
Cummins A053X172, §4 Installation, clearance requirements - 5 ft (1524 mm)structure · oppositeSide
The opposite engine/alternator side at not less than 60 in from a combustible wall, with 18 in of that unobstructed for service.
“The opposite side must be located not less than 60 inches (1524 mm) from any structures having combustible walls. A minimum of 18 inches (458 mm) of unobstructed space is required for service access.”
Cummins A053X172, §4 Installation, clearance requirements - 30 in (762 mm)structure · intakeSide
Cooling air intake side at not less than 30 in from a combustible wall, free of obstructions to air flow and service access.
“The intake (cooling air inlet) side of the generator set must be located not less than 30 inches (762 mm) from any structures having combustible walls. This space must be free of obstructions to air flow and service access.”
Cummins A053X172, §4 Installation, clearance requirements - 5 ft (1524 mm)structure · dischargeSide
Air discharge side at not less than 60 in from a combustible wall, always unobstructed.
“The air discharge side must always be unobstructed and spaced a minimum of 60 inches (1524 mm) from any structures having combustible walls.”
Cummins A053X172, §4 Installation, clearance requirements - 3 ft (914 mm)combustibles · dischargeSide
36 in on the discharge side free of any combustible items and unobstructed for service access.
“A minimum of 36 inches (915 mm) must be free of any combustible items, and unobstructed for service access.”
Cummins A053X172, §4 Installation, clearance requirements
Kohler RESA / RESC residential
14RESA; 14RESAL; 20RESC; 20RESCL; 20RESA(L) (no longer available) · 14–20 kW
Source: Kohler, Installation — Residential/Commercial Generator Sets, TP-6803 2/21q
- 4 ft (1219 mm)combustibles · exhaustEnd
4 ft beyond the exhaust end clear of all combustible materials — plants, shrubs, building materials and lawn furniture.
“No plants, shrubs, or other combustible materials are allowed within 1.2 m (4 ft.) of the exhaust end of the generator set. … Clear all combustible materials, including plants and shrubs, building materials, and lawn furniture, from an area at least 1.2 m (4 ft.) beyond the exhaust end of the generator set.”
Kohler TP-6803, §1.4 Location and Mounting / §1.4.1 Mounting Area - 10 ft (3048 mm)airIntake · exhaustEnd
10 ft from furnace and other similar intakes, measured from the exhaust end.
“Furnace and other similar intakes must be at least 3 m (10 ft.) from the exhaust end of the generator set.”
Kohler TP-6803, §1.3–1.4
Not published — structure
TP-6803 publishes NO numeric distance from the set to a structure in its body text. It defers the figure to state and local codes and to the model dimension drawing in Section 3, which is a drawing rather than text. Read the figure off the dimension drawing for your exact model, and check it against your local code — do not assume another manufacturer's number.
“The required distance from a structure is dependent on state and local codes. See the dimension drawing in Section 3 for the minimum clearance from structures and non-combustible materials.”
Model code
NFPA 37 §4.1.4 — engines located outdoors
NFPA 37 is not freely redistributable and we do not hold a copy. This text is quoted as reproduced verbatim in the Generac installation guidelines, pp. 15–16. Verify against the standard itself before relying on it for a submission.
- 5 ft (1524 mm)
At least 5 ft from openings in walls.
“Engines, and their weatherproof housings if provided, installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from structures having combustible walls.”
Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 as reproduced - 5 ft (1524 mm)
At least 5 ft from structures having combustible walls.
“Engines, and their weatherproof housings if provided, installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from structures having combustible walls.”
Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 as reproduced
NFPA 37 §4.1.3 — roofs, platforms, decks and other supporting structures
NFPA 37 is not freely redistributable and we do not hold a copy. This text is quoted as reproduced verbatim in the Generac installation guidelines, pp. 15–16. Verify against the standard itself before relying on it for a submission.
- 18 in (457 mm)
18 in from structures having combustible walls.
“Generator can be located 18 in (457 mm) from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure. Surface beneath the generator and beyond must be noncombustible to a minimum distance of 12 in (30.5 cm).”
Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures - 5 ft (1524 mm)
5 ft from any operable opening in the structure.
“Generator can be located 18 in (457 mm) from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure.”
Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures - 1 ft (305 mm)
The surface beneath the generator and beyond must be non-combustible for at least 12 in.
“Surface beneath the generator and beyond must be noncombustible to a minimum distance of 12 in (30.5 cm). Contact local Building Inspection Department or fire department to determine which noncombustible materials are approved for installation.”
Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures
Jurisdictions
Village of Scarsdale, NY
Source: Village of Scarsdale, NY — Generator Setbacks
Lot-line setbacks by district
| District | Rear | Side |
|---|---|---|
| Residence AA-1 | 15 ft (4572 mm) | 20 ft (6096 mm) |
| Residence A-1 | 10 ft (3048 mm) | 10 ft (3048 mm) |
| Residence A-2 | 5 ft (1524 mm) | 10 ft (3048 mm) |
| Residence A-2a | 5 ft (1524 mm) | 10 ft (3048 mm) |
| Residence A-3 | 5 ft (1524 mm) | 5 ft (1524 mm) |
| Residence A-4 | 3 ft (914 mm) | 3 ft (914 mm) |
| Residence A-5 | 3 ft (914 mm) | 3 ft (914 mm) |
Permitted locations
The unit must go in the principal or an accessory building, in a purpose-built underground enclosure, or in the rear or side yard. Not the front yard.
“Permanent standby generators must be placed in the principal or accessory building or in an underground facility constructed purposely to house a generator or in the rear or side yard of any property”
Scarsdale NY, Generator Setbacks, placement paragraph Noise limit — 70 dBA at 23 ft, 66 dBA for side-yard siting in A-3/A-4/A-5
The manufacturer's sound specification must be submitted with the building permit application. Scarsdale caps the unit at 70 dBA measured 23 ft away, tightening to 66 dBA where the unit is sited in the side yard in the A-3, A-4 and A-5 districts. Check your model's published sound level before you commit to a side-yard position in those districts.
“Permanent standby generators shall not exceed 70 decibels on the A scale as measured 23 feet from the unit … except that permanent standby generators placed in the side yard in the A-3,A-4 and A-5 zoning districts shall not exceed 66 decibels on the A scale as measured 23 feet from the unit”
Scarsdale NY, Generator Setbacks, noise paragraphs Application required before installation
An application must be filed with the Building Department before installation.
“All property owners seeking to install a permanent standby generator must file an application with the Building Department prior to installation.”
Scarsdale NY, Generator Setbacks, application paragraph
Township of Wall, NJ
Source: Township of Wall, NJ — Standby Generator Allowable Locations
- 5 ft (1524 mm)
5 ft from any combustible building.
“Standby Generators are required to be 5 feet from any combustible building, except where the weatherproof enclosure is constructed of noncombustible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure, and then they may be placed at least 18 inches from the structure.”
Wall Twp NJ, Clearance from Structure - 5 ft (1524 mm)
5 ft from any window, door or opening into the building, measured from any part of the generator. Wall Township states this limb has no exceptions.
“All generators must be at least 5 feet from any window door or opening into the building. (This measurement is from any part of the generator) … 5 foot from any window, door or opening into the house. (no exceptions to this rule)”
Wall Twp NJ, Clearance from Windows, Doors and Openings in the Building
Rear and side yard setbacks for the zone still apply
Wall Township does not publish a generator-specific lot-line figure. The generator must meet the ordinary rear and side yard setbacks for its zone, so read those from the zoning schedule for your district. Front yard siting is not permitted, and corner lots have two front yards.
“Generators must meet the required rear and side yard setbacks for the zone. Generators are not permitted in the front yard area (corner lots have two front yards pursuant to Township Ordinance).”
Wall Twp NJ, Land Use (Zoning) Requirements Evergreen screening is mandatory
The unit must be entirely shielded from view by an existing or proposed evergreen buffer, shown on the submitted plan with tree type and size. Fences, pools and sheds do not count as a buffer.
“Generators must be entirely shielded from view by an existing or proposed evergreen buffer. Fences, pools, sheds etc. are not valid evergreen buffers. This buffer must be shown on the plan submitted and include type and size of trees.”
Wall Twp NJ, Land Use (Zoning) Requirements
Pemberton Township, NJ
Source: Pemberton Township, NJ — Residential Generators
- 5 ft (1524 mm)
No closer than 5 ft from a property line, on the side or rear of the property.
“Permanently installed generators must be placed on side or rear of the property no closer than 5 feet from a property line and no further than 15 feet from the building being served.”
Pemberton Twp NJ, Zoning application, item 2 - max 15 ft (4572 mm)
No FURTHER than 15 ft from the building being served. This is a maximum, not a minimum — it can conflict with the clearance minima on a tight lot.
“Permanently installed generators must be placed on side or rear of the property no closer than 5 feet from a property line and no further than 15 feet from the building being served.”
Pemberton Twp NJ, Zoning application, item 2
Unit size and output are capped
The unit and pad together may not exceed 15 square feet or 4 ft in height, and the generator may not exceed 24 kW output. Check your model's pad footprint against this before ordering.
“Provide the dimensions of the unit itself including the pad. The unit and pad cannot be larger than 15 square feet, maximum height 4 feet, and provide maximum output of 24 kW.”
Pemberton Twp NJ, Zoning application, item 3 Utility gas-pressure letter required
A letter from the utility confirming adequate gas pressure for the generator must be obtained as part of the zoning application.
“Obtain a letter from your utility company confirming that there is adequate gas pressure supplied to the property to handle the generator.”
Pemberton Twp NJ, Zoning application, item 4 Front yard only by exception, with screening
If the only practical location is the front of the property due to utility location or other circumstance, permanent screening or landscaping must be installed and maintained by the homeowner.
“If the only practical location is in the front of the property due to utility location or other circumstance, permanent screening or landscaping must be installed and maintained by the homeowner.”
Pemberton Twp NJ, Zoning application, item 2
Leon County, FL
Source: Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020 · effective 2023-12-31
- 10 ft (3048 mm)
Exhaust termination a minimum of 10 ft from any opening that could admit fumes — DOUBLE the NFPA 37 figure, and stricter than every manufacturer diagram here.
“Permanently installed residential standby generator's exhaust shall be located to not create a nuisance. Exhaust termination shall be a minimum of 10 feet (3048 mm) from any openings that could allow fumes into the building (doors, operable windows, eave vents, etc.) or air intakes.”
FBC Residential §M1905.2.5 Exhaust location
Wind resistance — 120 mph ultimate design wind speed minimum
Generators exposed to wind must be designed and installed to resist wind pressures based on a minimum 120 mph ultimate design wind speed. If the manufacturer's installation requirements do not specify the wind resistance of the anchoring method, a Florida-licensed engineer must certify that the method meets it. Budget for that certification — it is the item most likely to delay a Florida permit.
“Per FBC, Residential M1905.2.4, generators that are exposed to the wind shall be designed and installed to resist wind pressures based on a minimum of 120mph ultimate design wind speed. If the generator manufacturer installation requirements do not specify the wind resistance of the installation/anchoring method, a State of Florida licensed engineer will be required to certify that the installation/anchoring method meets the wind resistance requirements specified above.”
FBC Residential §M1905.2.4 Wind resistance, as applied by Leon County Flood elevation
In flood hazard areas the unit must be located or installed per FBC Residential R322.1.6. Leon County requires a Flood Letter Certification Form prepared by a Florida engineer at submittal, and as-built elevation documentation after installation if the property is flood prone.
“In flood hazard areas as established by Table R301.2(1), permanently installed stand-by generators shall be located or installed in accordance with Section R322.1.6.”
FBC Residential §M1905.2.2 Flood hazard Listed and labelled, installed to the listing
The unit must be listed and labelled for the application, and installed in compliance with the manufacturer's installation instructions and listing conditions.
“Permanently installed stand-by generators regulated by this code shall be listed and labeled for the application in which they are installed and used. … Installation of permanently installed stand-by generators shall comply with manufacturer's installation instructions and listing conditions.”
FBC Residential §M1905.1 and §M1905.2
The whole dataset is also available as JSON at /api/reference, and over MCP — see the MCP documentation.