{"coverage":{"statement":"SetbackCalc ships verified data for the manufacturer families and jurisdictions listed here and nothing else. Anything absent is absent because we have not verified it, not because it has no requirements. We do not claim nationwide coverage.","manufacturerFamilies":3,"jurisdictions":4,"hoa":"HOA and deed restrictions (CC&Rs) are not checked. There is no public per-address source for them, so we do not pretend to have one. CC&Rs routinely impose screening, placement and noise terms stricter than anything above, and they are enforceable against you independently of the building permit. Read your CC&Rs, and get any HOA architectural-review approval in writing before the pad is poured."},"aspects":{"structure":{"label":"Structure / combustible wall","blurb":"Distance from the generator to the wall of a structure."},"opening":{"label":"Operable opening","blurb":"Distance to any operable window, door, vent, window well, eave/soffit vent or other opening through which exhaust could enter an occupied structure."},"airIntake":{"label":"Mechanical air intake","blurb":"Distance to an HVAC or furnace outdoor air intake, which draws air inward under power and is treated separately from a passive opening."},"combustibles":{"label":"Combustible materials","blurb":"Distance to plants, shrubs, trees, building materials and lawn furniture."},"serviceAccess":{"label":"Service access","blurb":"Space that must stay clear so the unit can be maintained and panels removed."},"propertyLine":{"label":"Property line","blurb":"Zoning setback from the lot line."},"buildingServed":{"label":"Building served","blurb":"Distance to the building the generator supplies."}},"manufacturers":[{"id":"generac-air-cooled","manufacturer":"Generac","family":"Air-cooled home standby","models":["Guardian and PowerPact air-cooled home standby, 9 kW–22 kW (60 Hz)"],"kwRange":"9–22 kW (the companion owner's manual covers 10–24 kW with the same placement guidance)","ratingsAffectClearances":false,"ratingsNote":"The source document gives one clearance set for the whole family. Clearance is not a function of kW rating in any family we have read.","fuelTypes":["natural-gas","lp-vapour"],"faces":[{"id":"rear","label":"Rear","description":"Fuel and electrical connections are made on this face; it is the face that sits toward the house."},{"id":"front","label":"Front","description":"Control panel and service access."},{"id":"endA","label":"Left end","description":"Enclosure end panel."},{"id":"endB","label":"Right end","description":"Enclosure end panel."},{"id":"top","label":"Overhead","description":"Vertical space above the enclosure."}],"sourceDocument":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","rules":[{"id":"generac-rear-wall","aspect":"structure","face":"rear","bound":"min","inches":18,"millimetres":457,"requirement":"18 in from an existing wall at the rear, where the fuel and electrical connections are made.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, items B and D","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, items B and D","quote":"Fuel and electrical connections are made here. 18 in (457 mm) minimum clearance per NFPA testing, labeling, and listing, unless state or local codes dictate otherwise. … The generator should not be placed closer than 18 in (457 mm) from existing walls.","sourceFile":"docs/generac-ac-install-guidelines.txt"},"exception":{"inches":60,"summary":"The 18 in figure is a listing-based reduction from NFPA 37's 5 ft. Where state or local codes do not accept the SwRI listing, the unreduced NFPA 37 §4.1.4 figure of 5 ft applies.","conditions":["State or local code declines the SwRI listing, which the manual expressly allows for (\"unless state or local codes dictate otherwise\")."],"citation":{"label":"Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 as reproduced","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 16, NFPA 37 §4.1.4 as reproduced","quote":"NFPA 37, Section 4.1.4, Engines Located Outdoors: Engines, and their weatherproof housings if provided, installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from structures having combustible walls.","sourceFile":"docs/generac-ac-install-guidelines.txt"}}},{"id":"generac-front-service","aspect":"serviceAccess","face":"front","bound":"min","inches":36,"millimetres":914,"requirement":"3 ft clear in front, including shrubs, bushes and trees.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, item A","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, item A","quote":"Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-endA-service","aspect":"serviceAccess","face":"endA","bound":"min","inches":36,"millimetres":914,"requirement":"3 ft clear at the ends, including shrubs, bushes and trees.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, item A","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, item A","quote":"Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-endB-service","aspect":"serviceAccess","face":"endB","bound":"min","inches":36,"millimetres":914,"requirement":"3 ft clear at the ends, including shrubs, bushes and trees.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, item A","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, item A","quote":"Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes shrubs, bushes, and trees.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-overhead","aspect":"structure","face":"top","bound":"min","inches":60,"millimetres":1524,"requirement":"5 ft from any structure, overhang or projection above the unit. Never under a wooden deck or structure.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, item F","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, item F","quote":"5 ft (1.52 m) minimum distance from any structure, overhang, or projections from wall. DO NOT install under wooden decks or structures.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-openings","aspect":"opening","face":"all","bound":"min","inches":60,"millimetres":1524,"requirement":"5 ft from any opening in a wall, measured from any point of the generator. The SwRI listing reduces the distance to the WALL, not the distance to OPENINGS.","citation":{"label":"Generac Install. Guidelines, Figure 3-2 item C, with NFPA 37 §4.1.4 at p. 16","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2 item C, with NFPA 37 §4.1.4 at p. 16","quote":"No operable windows, doors, vents, window wells, or openings in the wall are permitted near any point of the generator. … Engines … installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls …","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-hvac-intake","aspect":"airIntake","face":"all","bound":"min","inches":120,"millimetres":3048,"requirement":"10 ft horizontally from an HVAC supply-air outdoor intake opening.","citation":{"label":"Generac Install. Guidelines, p. 14, item J (Make up air system)","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 14, item J (Make up air system)","quote":"IMPORTANT NOTE: Mechanical and gravity outdoor air intake openings for HVAC supply air systems shall be located not less than 10 feet (3048mm) horizontally from the generator enclosure. See Section 401 in the ICC Mechanical Code for any additional requirements.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"generac-fence","aspect":"serviceAccess","face":"front","bound":"min","inches":36,"millimetres":914,"requirement":"A removable fence panel may not sit closer than 3 ft in front of the unit.","citation":{"label":"Generac Install. Guidelines, Figure 3-2, item E","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"Figure 3-2, item E","quote":"A removable barrier (non-permanent; without footings) installed as a visual surround. Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the generator.","sourceFile":"docs/generac-ac-install-guidelines.txt"}}],"unpublished":[]},{"id":"cummins-rs","manufacturer":"Cummins","family":"RS home standby","models":["RS13A","RS17A","RS20A","RS20AC"],"kwRange":"13–20 kW","ratingsAffectClearances":false,"ratingsNote":"The source document gives one clearance set for the whole family. Clearance is not a function of kW rating in any family we have read.","fuelTypes":["natural-gas","lp-vapour"],"faces":[{"id":"serviceSide","label":"Service side (engine or alternator side)","description":"Whichever of the engine/alternator sides you place toward the structure as the service side."},{"id":"oppositeSide","label":"Opposite side (engine or alternator side)","description":"The engine/alternator side opposite the service side."},{"id":"intakeSide","label":"Cooling air intake side","description":"The face the unit draws cooling air through."},{"id":"dischargeSide","label":"Air discharge side","description":"The face the unit discharges cooling air and exhaust through."}],"sourceDocument":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","rules":[{"id":"cummins-openings","aspect":"opening","face":"all","bound":"min","inches":60,"millimetres":1524,"requirement":"60 in from any opening in a wall of a structure that may be occupied, measured from ALL parts of the enclosure.","citation":{"label":"Cummins A053X172, §4 Installation, Picking a Location","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, Picking a Location","quote":"All parts of the generator set enclosure must be at least 60 inches (1524 mm) from any openings in walls of structures that may be occupied. Examples of wall openings include but are not limited to: operable windows, doors, dryer vents, fresh air intake for heaters, etc.","sourceFile":"docs/cummins-rs-install.txt"}},{"id":"cummins-service-side","aspect":"structure","face":"serviceSide","bound":"min","inches":18,"millimetres":457,"requirement":"One of the engine/alternator sides at not less than 18 in from a combustible wall, kept free of obstruction for service access.","citation":{"label":"Cummins A053X172, §4 Installation, clearance requirements","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, clearance requirements","quote":"One side (either engine or alternator) must be located not less than 18 inches (458 mm) from any structures having combustible walls. This space must be free of any obstructions for service access.","sourceFile":"docs/cummins-rs-install.txt"}},{"id":"cummins-opposite-side","aspect":"structure","face":"oppositeSide","bound":"min","inches":60,"millimetres":1524,"requirement":"The opposite engine/alternator side at not less than 60 in from a combustible wall, with 18 in of that unobstructed for service.","citation":{"label":"Cummins A053X172, §4 Installation, clearance requirements","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, clearance requirements","quote":"The opposite side must be located not less than 60 inches (1524 mm) from any structures having combustible walls. A minimum of 18 inches (458 mm) of unobstructed space is required for service access.","sourceFile":"docs/cummins-rs-install.txt"}},{"id":"cummins-intake-side","aspect":"structure","face":"intakeSide","bound":"min","inches":30,"millimetres":762,"requirement":"Cooling air intake side at not less than 30 in from a combustible wall, free of obstructions to air flow and service access.","citation":{"label":"Cummins A053X172, §4 Installation, clearance requirements","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, clearance requirements","quote":"The intake (cooling air inlet) side of the generator set must be located not less than 30 inches (762 mm) from any structures having combustible walls. This space must be free of obstructions to air flow and service access.","sourceFile":"docs/cummins-rs-install.txt"}},{"id":"cummins-discharge-side","aspect":"structure","face":"dischargeSide","bound":"min","inches":60,"millimetres":1524,"requirement":"Air discharge side at not less than 60 in from a combustible wall, always unobstructed.","citation":{"label":"Cummins A053X172, §4 Installation, clearance requirements","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, clearance requirements","quote":"The air discharge side must always be unobstructed and spaced a minimum of 60 inches (1524 mm) from any structures having combustible walls.","sourceFile":"docs/cummins-rs-install.txt"}},{"id":"cummins-discharge-combustibles","aspect":"combustibles","face":"dischargeSide","bound":"min","inches":36,"millimetres":914,"requirement":"36 in on the discharge side free of any combustible items and unobstructed for service access.","citation":{"label":"Cummins A053X172, §4 Installation, clearance requirements","document":"Cummins, Installation Manual A053X172 (Issue 16), 5-2019","reference":"§4 Installation, clearance requirements","quote":"A minimum of 36 inches (915 mm) must be free of any combustible items, and unobstructed for service access.","sourceFile":"docs/cummins-rs-install.txt"}}],"unpublished":[]},{"id":"kohler-resa-resc","manufacturer":"Kohler","family":"RESA / RESC residential","models":["14RESA","14RESAL","20RESC","20RESCL","20RESA(L) (no longer available)"],"kwRange":"14–20 kW","ratingsAffectClearances":false,"ratingsNote":"The source document gives one clearance set for the whole family. Clearance is not a function of kW rating in any family we have read.","fuelTypes":["natural-gas","lp-vapour"],"faces":[{"id":"exhaustEnd","label":"Exhaust end","description":"The end the engine exhaust mixes with cooling air and leaves the enclosure."},{"id":"other","label":"Other faces","description":"Remaining faces of the enclosure."}],"sourceDocument":"Kohler, Installation — Residential/Commercial Generator Sets, TP-6803 2/21q","rules":[{"id":"kohler-combustibles","aspect":"combustibles","face":"exhaustEnd","bound":"min","inches":48,"millimetres":1219,"requirement":"4 ft beyond the exhaust end clear of all combustible materials — plants, shrubs, building materials and lawn furniture.","citation":{"label":"Kohler TP-6803, §1.4 Location and Mounting / §1.4.1 Mounting Area","document":"Kohler, Installation — Residential/Commercial Generator Sets, TP-6803 2/21q","reference":"§1.4 Location and Mounting / §1.4.1 Mounting Area","quote":"No plants, shrubs, or other combustible materials are allowed within 1.2 m (4 ft.) of the exhaust end of the generator set. … Clear all combustible materials, including plants and shrubs, building materials, and lawn furniture, from an area at least 1.2 m (4 ft.) beyond the exhaust end of the generator set.","sourceFile":"docs/kohler-rca-install.txt"}},{"id":"kohler-intakes","aspect":"airIntake","face":"exhaustEnd","bound":"min","inches":120,"millimetres":3048,"requirement":"10 ft from furnace and other similar intakes, measured from the exhaust end.","citation":{"label":"Kohler TP-6803, §1.3–1.4","document":"Kohler, Installation — Residential/Commercial Generator Sets, TP-6803 2/21q","reference":"§1.3–1.4","quote":"Furnace and other similar intakes must be at least 3 m (10 ft.) from the exhaust end of the generator set.","sourceFile":"docs/kohler-rca-install.txt"}}],"unpublished":[{"aspect":"structure","requirement":"TP-6803 publishes NO numeric distance from the set to a structure in its body text. It defers the figure to state and local codes and to the model dimension drawing in Section 3, which is a drawing rather than text. Read the figure off the dimension drawing for your exact model, and check it against your local code — do not assume another manufacturer's number.","citation":{"label":"Kohler TP-6803, §1.4 Location and Mounting","document":"Kohler, Installation — Residential/Commercial Generator Sets, TP-6803 2/21q","reference":"§1.4 Location and Mounting","quote":"The required distance from a structure is dependent on state and local codes. See the dimension drawing in Section 3 for the minimum clearance from structures and non-combustible materials.","sourceFile":"docs/kohler-rca-install.txt"}}]}],"modelCode":[{"id":"nfpa37-ground","label":"NFPA 37 §4.1.4 — engines located outdoors","provenanceNote":"NFPA 37 is not freely redistributable and we do not hold a copy. This text is quoted as reproduced verbatim in the Generac installation guidelines, pp. 15–16. Verify against the standard itself before relying on it for a submission.","rules":[{"id":"nfpa37-openings","aspect":"opening","bound":"min","inches":60,"millimetres":1524,"requirement":"At least 5 ft from openings in walls.","citation":{"label":"Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 as reproduced","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 16, NFPA 37 §4.1.4 as reproduced","quote":"Engines, and their weatherproof housings if provided, installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from structures having combustible walls.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"nfpa37-structure","aspect":"structure","bound":"min","inches":60,"millimetres":1524,"requirement":"At least 5 ft from structures having combustible walls.","citation":{"label":"Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 as reproduced","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 16, NFPA 37 §4.1.4 as reproduced","quote":"Engines, and their weatherproof housings if provided, installed outdoors shall be located at least 5 ft (1.52 m) from openings in walls and at least 5 ft (1.52 m) from structures having combustible walls.","sourceFile":"docs/generac-ac-install-guidelines.txt"},"exception":{"inches":null,"summary":"No minimum separation is required where the adjacent wall has a one-hour fire resistance rating, or where the enclosure is non-combustible and a fire inside it has been demonstrated not to ignite combustibles outside it. Generac's SwRI full-scale fire test is that demonstration, and is what supports the 18 in rear figure.","conditions":["The adjacent wall of the structure has a fire resistance rating of at least one hour; or","The weatherproof enclosure is constructed of non-combustible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure."],"citation":{"label":"Generac Install. Guidelines, p. 16, NFPA 37 §4.1.4 and Annex A4.1.4(2) as reproduced","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 16, NFPA 37 §4.1.4 and Annex A4.1.4(2) as reproduced","quote":"A minimum separation shall not be required where the following conditions exist: 1. The adjacent wall of the structure has a fire resistance rating of at least one hour. 2. The weatherproof enclosure is constructed of noncombustible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure.","sourceFile":"docs/generac-ac-install-guidelines.txt"}}}]},{"id":"nfpa37-elevated","label":"NFPA 37 §4.1.3 — roofs, platforms, decks and other supporting structures","provenanceNote":"NFPA 37 is not freely redistributable and we do not hold a copy. This text is quoted as reproduced verbatim in the Generac installation guidelines, pp. 15–16. Verify against the standard itself before relying on it for a submission.","rules":[{"id":"nfpa37-elev-structure","aspect":"structure","bound":"min","inches":18,"millimetres":457,"requirement":"18 in from structures having combustible walls.","citation":{"label":"Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","quote":"Generator can be located 18 in (457 mm) from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure. Surface beneath the generator and beyond must be noncombustible to a minimum distance of 12 in (30.5 cm).","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"nfpa37-elev-openings","aspect":"opening","bound":"min","inches":60,"millimetres":1524,"requirement":"5 ft from any operable opening in the structure.","citation":{"label":"Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","quote":"Generator can be located 18 in (457 mm) from structures having combustible walls and 5 ft (1.52 m) from any operable opening in the structure.","sourceFile":"docs/generac-ac-install-guidelines.txt"}},{"id":"nfpa37-elev-noncombustible-surface","aspect":"combustibles","bound":"min","inches":12,"millimetres":305,"requirement":"The surface beneath the generator and beyond must be non-combustible for at least 12 in.","citation":{"label":"Generac Install. Guidelines, p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","document":"Generac, Installation Guidelines for 60 Hz Air-Cooled Generators (10000006541 Rev E)","reference":"p. 17, Placement on Roofs, Platforms, and Other Supporting Structures","quote":"Surface beneath the generator and beyond must be noncombustible to a minimum distance of 12 in (30.5 cm). Contact local Building Inspection Department or fire department to determine which noncombustible materials are approved for installation.","sourceFile":"docs/generac-ac-install-guidelines.txt"}}]}],"jurisdictions":[{"id":"scarsdale-ny","name":"Village of Scarsdale","state":"NY","sourceDocument":"Village of Scarsdale, NY — Generator Setbacks","rules":[],"districts":[{"id":"aa-1","label":"Residence AA-1","rules":[{"id":"scarsdale-aa-1-rear","aspect":"propertyLine","face":"rearLotLine","inches":180,"feet":15,"requirement":"15 ft from the rear lot line in Residence AA-1.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-aa-1-side","aspect":"propertyLine","face":"sideLotLine","inches":240,"feet":20,"requirement":"20 ft from the side lot line in Residence AA-1.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-1","label":"Residence A-1","rules":[{"id":"scarsdale-a-1-rear","aspect":"propertyLine","face":"rearLotLine","inches":120,"feet":10,"requirement":"10 ft from the rear lot line in Residence A-1.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-1-side","aspect":"propertyLine","face":"sideLotLine","inches":120,"feet":10,"requirement":"10 ft from the side lot line in Residence A-1.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-2","label":"Residence A-2","rules":[{"id":"scarsdale-a-2-rear","aspect":"propertyLine","face":"rearLotLine","inches":60,"feet":5,"requirement":"5 ft from the rear lot line in Residence A-2.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-2-side","aspect":"propertyLine","face":"sideLotLine","inches":120,"feet":10,"requirement":"10 ft from the side lot line in Residence A-2.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-2a","label":"Residence A-2a","rules":[{"id":"scarsdale-a-2a-rear","aspect":"propertyLine","face":"rearLotLine","inches":60,"feet":5,"requirement":"5 ft from the rear lot line in Residence A-2a.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-2a-side","aspect":"propertyLine","face":"sideLotLine","inches":120,"feet":10,"requirement":"10 ft from the side lot line in Residence A-2a.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-3","label":"Residence A-3","rules":[{"id":"scarsdale-a-3-rear","aspect":"propertyLine","face":"rearLotLine","inches":60,"feet":5,"requirement":"5 ft from the rear lot line in Residence A-3.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-3-side","aspect":"propertyLine","face":"sideLotLine","inches":60,"feet":5,"requirement":"5 ft from the side lot line in Residence A-3.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-4","label":"Residence A-4","rules":[{"id":"scarsdale-a-4-rear","aspect":"propertyLine","face":"rearLotLine","inches":36,"feet":3,"requirement":"3 ft from the rear lot line in Residence A-4.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-4-side","aspect":"propertyLine","face":"sideLotLine","inches":36,"feet":3,"requirement":"3 ft from the side lot line in Residence A-4.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"a-5","label":"Residence A-5","rules":[{"id":"scarsdale-a-5-rear","aspect":"propertyLine","face":"rearLotLine","inches":36,"feet":3,"requirement":"3 ft from the rear lot line in Residence A-5.","citation":{"label":"Scarsdale NY, Generator Setbacks, rear lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, rear lot line schedule","quote":"Permanent standby emergency-only generators shall be set back from the REAR LOT LINE at least: In a Residence AA-1 District: 15 Feet; In a Residence A-1 District: 10 Feet; In a Residence A-2, A-2a or A-3 Districts: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"id":"scarsdale-a-5-side","aspect":"propertyLine","face":"sideLotLine","inches":36,"feet":3,"requirement":"3 ft from the side lot line in Residence A-5.","citation":{"label":"Scarsdale NY, Generator Setbacks, side lot line schedule","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, side lot line schedule","quote":"Permanent standby emergency-only generators shall be setback from SIDE LOT LINE at least: In a Residence AA-1 District: 20 Feet; In a Residence A-1, A-2 or A-2a District: 10 Feet; In a Residence A-3 District: 5 Feet; In a Residence A-4, A-5 Districts: 3 Feet","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]}],"advisories":[{"title":"Permitted locations","body":"The unit must go in the principal or an accessory building, in a purpose-built underground enclosure, or in the rear or side yard. Not the front yard.","citation":{"label":"Scarsdale NY, Generator Setbacks, placement paragraph","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, placement paragraph","quote":"Permanent standby generators must be placed in the principal or accessory building or in an underground facility constructed purposely to house a generator or in the rear or side yard of any property","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"title":"Noise limit — 70 dBA at 23 ft, 66 dBA for side-yard siting in A-3/A-4/A-5","body":"The manufacturer's sound specification must be submitted with the building permit application. Scarsdale caps the unit at 70 dBA measured 23 ft away, tightening to 66 dBA where the unit is sited in the side yard in the A-3, A-4 and A-5 districts. Check your model's published sound level before you commit to a side-yard position in those districts.","citation":{"label":"Scarsdale NY, Generator Setbacks, noise paragraphs","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, noise paragraphs","quote":"Permanent standby generators shall not exceed 70 decibels on the A scale as measured 23 feet from the unit … except that permanent standby generators placed in the side yard in the A-3,A-4 and A-5 zoning districts shall not exceed 66 decibels on the A scale as measured 23 feet from the unit","sourceFile":"docs/scarsdale-generator-setbacks.txt"}},{"title":"Application required before installation","body":"An application must be filed with the Building Department before installation.","citation":{"label":"Scarsdale NY, Generator Setbacks, application paragraph","document":"Village of Scarsdale, NY — Generator Setbacks","reference":"Generator Setbacks, application paragraph","quote":"All property owners seeking to install a permanent standby generator must file an application with the Building Department prior to installation.","sourceFile":"docs/scarsdale-generator-setbacks.txt"}}]},{"id":"wall-nj","name":"Township of Wall","state":"NJ","sourceDocument":"Township of Wall, NJ — Standby Generator Allowable Locations","rules":[{"id":"wall-structure","aspect":"structure","face":"all","bound":"min","inches":60,"millimetres":1524,"requirement":"5 ft from any combustible building.","citation":{"label":"Wall Twp NJ, Clearance from Structure","document":"Township of Wall, NJ — Standby Generator Allowable Locations","reference":"Clearance from Structure","quote":"Standby Generators are required to be 5 feet from any combustible building, except where the weatherproof enclosure is constructed of noncombustible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure, and then they may be placed at least 18 inches from the structure.","sourceFile":"docs/wallnj-generator-locations.txt"},"exception":{"inches":18,"summary":"18 in where the enclosure is non-combustible and a fire inside it has been demonstrated not to ignite combustibles outside. Wall Township states the manufacturer holds that information.","conditions":["The weatherproof enclosure is constructed of noncombustible materials, and","it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure (obtain the demonstration from the manufacturer)."],"citation":{"label":"Wall Twp NJ, Clearance from Structure","document":"Township of Wall, NJ — Standby Generator Allowable Locations","reference":"Clearance from Structure","quote":"except where the weatherproof enclosure is constructed of noncombustible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure, and then they may be placed at least 18 inches from the structure. The information about the enclosure is available from the manufacturer.","sourceFile":"docs/wallnj-generator-locations.txt"}}},{"id":"wall-openings","aspect":"opening","face":"all","bound":"min","inches":60,"millimetres":1524,"requirement":"5 ft from any window, door or opening into the building, measured from any part of the generator. Wall Township states this limb has no exceptions.","citation":{"label":"Wall Twp NJ, Clearance from Windows, Doors and Openings in the Building","document":"Township of Wall, NJ — Standby Generator Allowable Locations","reference":"Clearance from Windows, Doors and Openings in the Building","quote":"All generators must be at least 5 feet from any window door or opening into the building. (This measurement is from any part of the generator) … 5 foot from any window, door or opening into the house. (no exceptions to this rule)","sourceFile":"docs/wallnj-generator-locations.txt"}}],"advisories":[{"title":"Rear and side yard setbacks for the zone still apply","body":"Wall Township does not publish a generator-specific lot-line figure. The generator must meet the ordinary rear and side yard setbacks for its zone, so read those from the zoning schedule for your district. Front yard siting is not permitted, and corner lots have two front yards.","citation":{"label":"Wall Twp NJ, Land Use (Zoning) Requirements","document":"Township of Wall, NJ — Standby Generator Allowable Locations","reference":"Land Use (Zoning) Requirements","quote":"Generators must meet the required rear and side yard setbacks for the zone. Generators are not permitted in the front yard area (corner lots have two front yards pursuant to Township Ordinance).","sourceFile":"docs/wallnj-generator-locations.txt"}},{"title":"Evergreen screening is mandatory","body":"The unit must be entirely shielded from view by an existing or proposed evergreen buffer, shown on the submitted plan with tree type and size. Fences, pools and sheds do not count as a buffer.","citation":{"label":"Wall Twp NJ, Land Use (Zoning) Requirements","document":"Township of Wall, NJ — Standby Generator Allowable Locations","reference":"Land Use (Zoning) Requirements","quote":"Generators must be entirely shielded from view by an existing or proposed evergreen buffer. Fences, pools, sheds etc. are not valid evergreen buffers. This buffer must be shown on the plan submitted and include type and size of trees.","sourceFile":"docs/wallnj-generator-locations.txt"}}]},{"id":"pemberton-nj","name":"Pemberton Township","state":"NJ","sourceDocument":"Pemberton Township, NJ — Residential Generators","rules":[{"id":"pemberton-lot-line","aspect":"propertyLine","face":"anyLotLine","bound":"min","inches":60,"millimetres":1524,"requirement":"No closer than 5 ft from a property line, on the side or rear of the property.","citation":{"label":"Pemberton Twp NJ, Zoning application, item 2","document":"Pemberton Township, NJ — Residential Generators","reference":"Zoning application, item 2","quote":"Permanently installed generators must be placed on side or rear of the property no closer than 5 feet from a property line and no further than 15 feet from the building being served.","sourceFile":"docs/pembertonnj-generators.txt"}},{"id":"pemberton-building-served","aspect":"buildingServed","face":"all","bound":"max","inches":180,"millimetres":4572,"requirement":"No FURTHER than 15 ft from the building being served. This is a maximum, not a minimum — it can conflict with the clearance minima on a tight lot.","citation":{"label":"Pemberton Twp NJ, Zoning application, item 2","document":"Pemberton Township, NJ — Residential Generators","reference":"Zoning application, item 2","quote":"Permanently installed generators must be placed on side or rear of the property no closer than 5 feet from a property line and no further than 15 feet from the building being served.","sourceFile":"docs/pembertonnj-generators.txt"}}],"advisories":[{"title":"Unit size and output are capped","body":"The unit and pad together may not exceed 15 square feet or 4 ft in height, and the generator may not exceed 24 kW output. Check your model's pad footprint against this before ordering.","citation":{"label":"Pemberton Twp NJ, Zoning application, item 3","document":"Pemberton Township, NJ — Residential Generators","reference":"Zoning application, item 3","quote":"Provide the dimensions of the unit itself including the pad. The unit and pad cannot be larger than 15 square feet, maximum height 4 feet, and provide maximum output of 24 kW.","sourceFile":"docs/pembertonnj-generators.txt"}},{"title":"Utility gas-pressure letter required","body":"A letter from the utility confirming adequate gas pressure for the generator must be obtained as part of the zoning application.","citation":{"label":"Pemberton Twp NJ, Zoning application, item 4","document":"Pemberton Township, NJ — Residential Generators","reference":"Zoning application, item 4","quote":"Obtain a letter from your utility company confirming that there is adequate gas pressure supplied to the property to handle the generator.","sourceFile":"docs/pembertonnj-generators.txt"}},{"title":"Front yard only by exception, with screening","body":"If the only practical location is the front of the property due to utility location or other circumstance, permanent screening or landscaping must be installed and maintained by the homeowner.","citation":{"label":"Pemberton Twp NJ, Zoning application, item 2","document":"Pemberton Township, NJ — Residential Generators","reference":"Zoning application, item 2","quote":"If the only practical location is in the front of the property due to utility location or other circumstance, permanent screening or landscaping must be installed and maintained by the homeowner.","sourceFile":"docs/pembertonnj-generators.txt"}}]},{"id":"leon-county-fl","name":"Leon County","state":"FL","effective":"2023-12-31","sourceDocument":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","rules":[{"id":"fbc-exhaust-openings","aspect":"opening","face":"all","bound":"min","inches":120,"millimetres":3048,"requirement":"Exhaust termination a minimum of 10 ft from any opening that could admit fumes — DOUBLE the NFPA 37 figure, and stricter than every manufacturer diagram here.","citation":{"label":"FBC Residential §M1905.2.5 Exhaust location","document":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","reference":"§M1905.2.5 Exhaust location","quote":"Permanently installed residential standby generator's exhaust shall be located to not create a nuisance. Exhaust termination shall be a minimum of 10 feet (3048 mm) from any openings that could allow fumes into the building (doors, operable windows, eave vents, etc.) or air intakes.","sourceFile":"docs/leoncountyfl-generator-requirements.txt"},"exception":{"inches":60,"summary":"5 ft is permitted, or the manufacturer's figure if more restrictive, but ONLY where the carbon monoxide alarm conditions are met.","conditions":["A CO alarm is installed within 10 ft of each room used for sleeping purposes, or per the alarm manufacturer's requirements and listing, whichever is more restrictive; and","an additional CO alarm is installed as close as possible to the building's exterior opening nearest the generator exhaust; and","BOTH of those CO alarms are of a type required by FBC Residential §R315.1.1 or §R315.1.2 — the code's own third condition, so an alarm that does not meet those sections does not unlock this exception; and","the manufacturer's own installation requirement is met where it is more restrictive than 5 ft."],"citation":{"label":"FBC Residential §M1905.2.5 Exception","document":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","reference":"§M1905.2.5 Exception","quote":"Exception: The generator exhaust can be located a minimum of 5 feet (1524 mm) from any such openings (doors, operable windows, eave vents, etc.) or in compliance with generator manufacturer installation requirements and listing, whichever is more restrictive, if all of the following are complied with: 1. A carbon monoxide (CO) alarm(s) is installed in the residency within 10 feet (3048 mm) of each room used for sleeping purposes … 2. An additional carbon monoxide (CO) alarm is installed in the residency as close as possible to the building's exterior opening nearest to the generator exhaust. 3. The carbon monoxide (CO) alarms mentioned above shall be of the types required by Sections R315.1.1 or R315.1.2 of this code.","sourceFile":"docs/leoncountyfl-generator-requirements.txt"}}}],"advisories":[{"title":"Wind resistance — 120 mph ultimate design wind speed minimum","body":"Generators exposed to wind must be designed and installed to resist wind pressures based on a minimum 120 mph ultimate design wind speed. If the manufacturer's installation requirements do not specify the wind resistance of the anchoring method, a Florida-licensed engineer must certify that the method meets it. Budget for that certification — it is the item most likely to delay a Florida permit.","citation":{"label":"FBC Residential §M1905.2.4 Wind resistance, as applied by Leon County","document":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","reference":"§M1905.2.4 Wind resistance, as applied by Leon County","quote":"Per FBC, Residential M1905.2.4, generators that are exposed to the wind shall be designed and installed to resist wind pressures based on a minimum of 120mph ultimate design wind speed. If the generator manufacturer installation requirements do not specify the wind resistance of the installation/anchoring method, a State of Florida licensed engineer will be required to certify that the installation/anchoring method meets the wind resistance requirements specified above.","sourceFile":"docs/leoncountyfl-generator-requirements.txt"}},{"title":"Flood elevation","body":"In flood hazard areas the unit must be located or installed per FBC Residential R322.1.6. Leon County requires a Flood Letter Certification Form prepared by a Florida engineer at submittal, and as-built elevation documentation after installation if the property is flood prone.","citation":{"label":"FBC Residential §M1905.2.2 Flood hazard","document":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","reference":"§M1905.2.2 Flood hazard","quote":"In flood hazard areas as established by Table R301.2(1), permanently installed stand-by generators shall be located or installed in accordance with Section R322.1.6.","sourceFile":"docs/leoncountyfl-generator-requirements.txt"}},{"title":"Listed and labelled, installed to the listing","body":"The unit must be listed and labelled for the application, and installed in compliance with the manufacturer's installation instructions and listing conditions.","citation":{"label":"FBC Residential §M1905.1 and §M1905.2","document":"Leon County, FL — Permitting Requirements for Permanently Installed Stand-by Generators, Based on FBC 8th Edition (2023) and NEC 2020","reference":"§M1905.1 and §M1905.2","quote":"Permanently installed stand-by generators regulated by this code shall be listed and labeled for the application in which they are installed and used. … Installation of permanently installed stand-by generators shall comply with manufacturer's installation instructions and listing conditions.","sourceFile":"docs/leoncountyfl-generator-requirements.txt"}}]}],"findings":["Generac's air-cooled clearances do not vary by kW — one set covers the whole 9–22 kW family.","OEM geometries are not interchangeable: Cummins publishes per-face figures (18 in one engine/alternator side, 60 in the opposite, 30 in intake side, 60 in discharge side) where Generac publishes one rear figure around a symmetric envelope.","The SwRI listing reduces the distance to the WALL to 18 in. It does not reduce the 5 ft to OPENINGS. Conflating the two is the most common way a placement fails inspection.","Florida is materially stricter than NFPA 37: FBC Residential §M1905.2.5 requires 10 ft to openings, reducible to 5 ft only where the CO-alarm conditions are met. A placement drawn correctly off a manufacturer diagram still fails Florida Building Control.","Kohler TP-6803 publishes no numeric structure clearance in its body text and defers to state and local codes plus a dimension drawing. We flag that rather than guess it."]}